range | ComPact | |
---|---|---|
product name | ComPact NSX | |
range of product | ComPact NSX100...250 | |
device short name | NSX100B | |
product or component type | Circuit breaker | |
device application | Distribution | |
Number of poles | 3P | |
protected poles description | 3t | |
[In] rated current | 25 A at 40 °C | |
[Ue] rated operational voltage | 690 V AC 50/60 Hz | |
network type | AC | |
network frequency | 50/60 Hz | |
suitability for isolation | Yes conforming to EN/IEC 60947-2 | |
utilisation category | Category A | |
[Icu] rated ultimate short-circuit breaking capacity | 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 | |
Performance level | B 25 kA 415 V AC | |
trip unit name | TM-D | |
trip unit technology | Thermal-magnetic | |
trip unit protection functions | LI | |
control type | Toggle | |
Circuit breaker mounting mode | Fixed |
[Ui] rated insulation voltage | 800 V AC 50/60 Hz | |
---|---|---|
[Uimp] rated impulse withstand voltage | 8 kV | |
[Ics] rated service short-circuit breaking capacity | 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 | |
mechanical durability | 50000 cycles | |
electrical durability | 10000 cycles at 690 V In 20000 cycles at 690 V In/2 30000 cycles at 440 V In 50000 cycles at 440 V In/2 | |
mounting support | Backplate | |
upside connection | Front | |
downside connection | Front | |
connection pitch | 35 mm | |
protection type | L : for overload protection (thermal) I : for short-circuit protection (magnetic) | |
trip unit rating | 25 A at 40 °C | |
Long-time pick-up adjustment type Ir (thermal protection) | Adjustable | |
[Ir] long-time protection pick-up adjustment range | 0.7...1 x In | |
Long-time protection delay adjustment type tr | Fixed | |
[tr] long-time protection delay adjustment range | 120…400 s at 1.5 x In 15 s at 6 x Ir | |
Short-time protection pick-up adjustment type Isd | Fixed | |
[Isd] Short-time protection pick-up adjustment range | 300 A | |
Short-time protection delay adjustment type tsd | Fixed | |
earth-leakage protection | Without | |
Number of slots for electrical auxiliaries | 5 slot(s) | |
Width (W) | 105 mm | |
Height (H) | 161 mm | |
Depth (D) | 86 mm | |
net weight | 2.05 kg |
standards | EN/IEC 60947 | |
---|---|---|
product certifications | CCC EAC Marine | |
overvoltage category | Class II | |
electrical shock protection class | Class II | |
pollution degree | 3 conforming to IEC 60664-1 | |
IP degree of protection | IP40 conforming to IEC 60529 | |
IK degree of protection | IK07 conforming to IEC 62262 | |
ambient air temperature for operation | -25…70 °C | |
ambient air temperature for storage | -50…85 °C | |
relative humidity | 0…95 % | |
operating altitude | 0...2000 m without derating 2000 m...5000 m with derating |
Unit Type of Package 1 | PCE | |
---|---|---|
Number of Units in Package 1 | 1 | |
Package 1 Weight | 1.849 kg | |
Package 1 Height | 11.6 cm | |
Package 1 width | 14.4 cm | |
Package 1 Length | 19.3 cm |
Sustainable offer status | Green Premium product | |
---|---|---|
REACh Regulation | REACh Declaration | |
EU RoHS Directive | Compliant EU RoHS Declaration | |
Mercury free | Yes | |
RoHS exemption information | Yes | |
China RoHS Regulation | China RoHS declaration Product out of China RoHS scope. Substance declaration for your information | |
Environmental Disclosure | Product Environmental Profile | |
Circularity Profile | End of Life Information |
Warranty | 18 months |
---|